11. HOW TO DIAGNOSE THE TROUBLE

The pulse motor circuits are mounted to both indoor
and outdoor units. Therefore, diagnose troubles
according to the trouble diagnosis procedure as
described below. (Refer to the check points in
servicing written on the wiring diagrams attached to
the indoor/outdoor units.)

No.

1

2

3

4

5

6

Troubleshooting Procedure

First Confirmation

Primary Judgment

Judgment by Flashing LED of Indoor Unit

Self-Diagnosis by Remote Controller

Judgment of Trouble by Every Symptom

How to Check Simply the Main Parts

Page

80

81

81

82

85

95

Precautions when handling the new inverter (3DV Inverter)

! CAUTION: HIGH VOLTAGE

The high voltage circuit is incorporated.

Be careful to do the check service, as the electric shock may be caused in case of touching parts on the
P.C. board by hand.

The new inverter (3DV inverter) will be incorporated starting with this unit.

(3DV: 3-shunt Discrete Vector control)

!

!

!

!

!

The control circuitry has an uninsulated construction.

MCU

G-Tr

FET(6in1)

IGBT x 6

FET x 6

MCU

Separate
potential

Photocoupler

Photocoupler

Compressor

Compressor

Fan motor

Fan motor

Hall device

M18YAV-E, M18YACV-E (insulated type)

EAV-E, EACV-E series (uninsulated type)

Shared
potential

Driver

Driver

Amplifier

Amplifier

CAUTION!!

A high voltage (equivalent to the supply voltage) is also energized
to ground through the sensors, PMV and other low-voltage cir-
cuits. The sensor leads and other wires are covered with insulated
tubes for protection. Nevertheless, care must be taken to ensure
that these wires are not pinched.

CAUTION!!

Take sufficient care to avoid directly touching any of the circuit
parts without first turning off the power.

Sensor leads

Do NOT lay the circuit
board assembly flat.

CAUTION!!

At times such as when the circuit board is to be replaced, place the
circuit board assembly in a vertical position.

Laying the board flat on an electrically conductive object (such as the
top panel of the air conditioner's outdoor unit) while a charge is still
retained by the electrolytic capacitors of the inverter's main circuit may
cause short-circuiting between the electrolytic capacitors and second-
ary circuit components and result in damage to the components.

Table 11-1