10-5-2. Refrigerant Piping Connection

Flaring

1.

Cut the pipe with a pipe cutter.

2.

Insert a flare nut into the pipe, and flare the pipe.
Projection margin in flaring: A (Unit: mm)

Rigid (Clutch type)

Imperial (Wing nut type)

3.

Flaring size : B (Unit : mm)

In case of flaring for R410A with the conventional flare tool, pull it out approx. 0.5 mm more than that of R22 to adjust to the

specified flare size. The copper pipe gauge is useful for adjusting projection margin size.

Tighten the connection

Align the centers of the connecting pipes and tighten the flare nut as much as possible with your fingers. Then tighten the nut with a
wrench and torque wrench as shown in the figure.

(Unit: N·m)

Outer diameter of copper pipe

R410A tool used

Conventional tool used

6.35

0 to 0.5

1.0 to 1.5

9.52

0 to 0.5

1.0 to 1.5

12.7

0 to 0.5

1.0 to 1.5

Outer diameter of copper pipe

R410A

6.35

1.5 to 2.0

9.52

1.5 to 2.0

12.7

2.0 to 2.5

Outer diameter of copper pipe

B

R410A

R22

6.35

9.1

9.0

9.52

13.2

13.0

12.7

16.6

16.2

CAUTION

Do not apply excessive force. Otherwise, the nut may break.

Outer diameter of copper pipe

Tightening torque

6.

φ
φ
φ

35 mm

14 to 18 (1.4 to 1.8 kgf·m)

9.52 mm

33 to 42 (3.3 to 4.2 kgf·m)

12.7 mm

50 to 62 (5.0 to 6.2 kgf·m)

Obliquity

Roughness

Warp

Die

Pipe

+0
–0.4

Half union

Flare nut

Externally threaded side

Use a wrench to secure.

Internally threaded side

Use a torque wrench to tighten.

Flare at indoor
unit side

Flare at outdoor unit side