Description

Operation flow and applicable data, etc.

Item

1. Purpose

This function detects error on the
refrigerating cycle or error on the
compressor, and performs protective
control.

2. Operation

• Control of the compressor speed

The speed control is performed as
described in the left table based upon
the discharge temperature.

13. Discharge

tempera-
ture control

Control operation

Judges as an error and stops the compressor.

Reduce the compressor speed.

Reduce slowly compressor speed.

Keeps the compressor speed.

If the operation is performed with lower speed
than one commanded by the serial signal, speed
is slowly raised up to the commanded speed.

Operates with speed commanded by the serial
signal.

Td value

120˚C

115˚C

111˚C

108˚C

101˚C

1) Reset by RESET button.

2) Reset by RESET button or by the stop direction from

the remote controller.

* When the breaker is turned [ON] (In restart time

after power failure) or RESET button is pushed
while the FILTER indicator is turned on, the air
purifier is not turned on until the integrated opera-
tion time of the indoor fan exceeds 1 hour after
operation start (It is nor the air purifier operation
time).
It is the safety measures considering an incomplete
drain when electric dust collector has been cleaned
with water.

YES

NO

NO

NO

YES

YES

NO

NO

YES

Purifying operation

FILTER indicator ON

Purifier power OFF

Purifier power OFF

Purifier power ON

YES

Total

operation time

1000H

Error detection

Approx. 10 minutes

passed.

Error input

Purifier power ON

1 minute or less

FILTER incicator-OFF

continues.

FILTER indicator ON

Purifier power OFF

1

2

3

Error input

12. Air

purifying
control
[Detection
of abnor-
mality]

1. Purpose

The air purifying control function is to alert
the user to trouble in the ionizing or air
purifying operation.

2. Description

Trouble is determined to have occurred
(indicated by the FILTER indicator) in the
following four cases.

1) When a count of 1000H has been

reached on the timer

2) When the panel switch has been set to

OFF by the opening of the air inlet grile,
etc.

3) When an abnormal discharge caused

by a symptom such as the build-up of
dirt has been detected while the air
purifier is ON

4) When the electric dust collector has not

been installed correctly

* Trouble case (2) or (3) is deemed to

have occurred when the action
concerned continues for more than
one second.

3. Operation

The sequence that FILTER indicator is
turned on are described in the left flow-
chart.

!

When 1000H timer counts up, the
FILTER indicator keeps lighting even if
the operation is stopped by the remote
controller.
The timer is stored in memory of the
microcomputer, and the operation time
is cleared by filter RESET button on the
indoor unit or a power failure. (FILTER
indicator goes off.)

"

A trouble detected within 1 minute after
activation of the air is immediately
judged as an error and the FILTER
indicator goes on.

#

In case that 1 minute passed after
activation of the purifier, the purifier is
turned off while the PURE indicator
keeps ON. After 10 minutes passed,
restart the purifier and an error is
judged again.