beautypg.com

A.3 environmental requirements, Table a-9, Table a-10 – Sun Microsystems 6.0005E+11 User Manual

Page 224

background image

A-4

Ultra Enterprise 6000/5000/4000 Systems ManualNovember 1996

A

A.3 Environmental Requirements

BTU rating

4680 BTU

Power factor

0.92 - 0.96

Plug type

U.S.

NEMA 5-15P

International

10A, single phase IEC 320,
connected for 220-240 Vac

Table A-9 Cabinet Server Temperature, Humidity,

and Altitude Limits

Operating

Nonoperating

Temperature

41

°

F to 95

°

F (5

°

C to 35

°

C)*

-4

°

F to 140

°

F (-20

°

C to 60

°

C)

Humidity

20% to 80% RH noncondensing,
27C max wb

93% RH

Altitude

9,843 ft (3 km)

39,370 ft (12 km)

*Maximum operating temperature is 95

°

F (35

°

C) when using tape media.

Table A-10 Standalone Server Temperature, Humidity,

and Altitude Limits

Operating

Nonoperating

Temperature

41

°

F to 104

°

F (5

°

C to 40

°

C)*

-4

°

F to 140

°

F (-20

°

C to 60

°

C)

Humidity

20% to 80% RH noncondensing,
27C max wb

93% RH

Altitude

9,843 ft (3 km)

39,370 ft (12 km)

*Maximum operating temperature is 95

°

F (35

°

C) when using tape media.

Table A-8 Standalone Server Electrical Specifications (Continued)

Parameter

Value