beautypg.com

Technical data – IDEC FL1E SmartRelay User Manual

Page 329

background image

Technical data

IDEC SmartRelay Manual

315

Delay time at
• 0 to 1
• 1 to 0

typ. 1.5 ms

<1.0 ms (I3 ... I6)
typ. 1.5 ms

<1.0 ms (I3 ... I6)

typ. 1.5 ms

typ. 1.5 ms

Line length (unshielded)

100 m

100 m

Analog inputs
Number

4 (I1=AI3, I2=AI4,
I7=AI1, I8=AI2)

Range

0 ... 10 V DC

input impedance 72
k

Cycle time for analog value
generation

300 ms

max. Input voltage

28.8 V DC

Line length
(shielded and twisted)

10 m

Error limit

+/- 1.5 % at full scale

Digital outputs
Number

4

4

Output type

Relay outputs

Relay outputs

Electrical isolation

Yes

Yes

Dielectric Strength (between power/
input terminals and output terminals)

2,500 V AC, 1 minute
500 V DC, 1 minute

2,500 V AC, 1 minute
500 V DC, 1 minute

In groups of

1

1

Control of a digital input

Yes

Yes

Continuous current I

th (per terminal)

max. 10 A per relay

max. 5 A per relay

Surge current

max. 30 A

max. 30 A

Incandescent lamp load (25000
switching cycles) at

1000 W

1000 W

Fluorescent tubes with ballast
(25000 switching cycles)

10 x 58 W

10 x 58 W

Fluorescent tubes, conventionally
compensated
(25000 switching cycles)

1 x 58 W

1 x 58 W

Fluorescent tubes, uncompensated
(25000 switching cycles)

10 x 58 W

10 x 58 W

Derating

none; across the entire
temperature range

none; across the entire
temperature range

Short circuit-proof cos 1

Power protection B16,
600A

Power protection B16,
600A

FL1E-H12RCE

FL1E-B12RCE

FL1B-M08B2R2