IDEC FL1E SmartRelay User Manual
Page 146

IDEC SmartRelay functions
132
IDEC SmartRelay Manual
Parameter T
Note the defaults for parameter T in Chapter 4.3.2.
The time for parameter T can also be preset based on the
actual value of another, already-configured function. You
can use the actual values of the following functions:
• Analog comparator (actual value Ax - Ay, see Chapter
• Analog trigger (actual value Ax, see Chapter 4.4.16)
• Analog amplifier (actual value Ax, see Chapter 4.4.20)
• Analog multiplexer (actual value AQ, see Chapter 4.4.26)
• Analog ramp control (actual value AQ, see Chapter
• Analog math (actual value AQ, see Chapter 4.4.30)
• PI controller (actual value AQ, see Chapter 4.4.28)
• Counter (actual value Cnt, see Chapter 4.4.13)
Select the required function by the block number. The
timebase is adjustable. Please note the following listing:
Valid ranges of the timebase, if T = parameter
The display in programming mode (example):
B12 +R
T
=04:10h
Valid ranges of the timebase, if T = Actual value of an already-
programmed function
Timebase
max. value
min. resolution
Accuracy
s (seconds)
99:99
10 ms
+ 10 ms
m (minutes)
99:59
1s
+ 1 s
h (hours)
99:59
1 min
+ 1 min
Timebase
max. value
Meaning
Accuracy
ms
99990
Number of ms
+ 10 ms
s
5999
Number of s
+ 1 s
m
5999
Number of min
+ 1 min