Technical data – IDEC FL1E SmartRelay User Manual
Page 327
Technical data
IDEC SmartRelay Manual
313
Notice: For fluorescent lamps with capacitors, the technical data of fluorescent lamp
ballasts must also be considered. If the maximum allowed surge current is exceeded,
fluorescent lamps must be switched with appropriate contactor relays.
Control of a digital input
Yes
Continuous current I
th
max. 5 A per relay
Surge current
max. 30 A
Incandescent lamp load (25000 switching
cycles) at
1000 W
Fluorescent tubes with ballast (25000
switching cycles)
10 x 58 W
Fluorescent tubes, conventionally
compensated (25000 switching cycles)
1 x 58 W
Fluorescent tubes, uncompensated
(25000 switching cycles)
10 x 58 W
Derating
none; across the entire temperature range
Short circuit-proof cos 1
Power protection B16, 600A
Short circuit-proof cos 0.5 to 0.7
Power protection B16, 900A
Parallel output circuits for power increase Not permitted
Protection of output relay (if desired)
max. 16 A, characteristic B16
Minimum Switching Load
10 mA, 12 V DC
Initial Contact Resistance
100 m
maximum (at 1A, 24V DC)
Mechanical Life
10,000,000 operations minimum
(no load, 10 Hz)
Electrical Life
100,000 operations minimum (rated
resistive load, 1800 operations / hour)
Switching rate
Mechanical
10 Hz
Ohmic load/lamp load
2 Hz
Inductive load
0.5 Hz
FL1B-M08D2R2