IDEC SmartRelay functions
218
IDEC SmartRelay Manual
Parameters SP and Mq
The set-value SP and the value for Mq can be provided by
another already-programmed function. You can use the
actual values of the following functions:
• Analog comparator (actual value Ax - Ay, see Chapter
• Analog trigger (actual value Ax, see Chapter 4.4.16)
• Analog amplifier (actual value Ax, see Chapter 4.4.20)
• Analog multiplexer (actual value AQ, see Chapter 4.4.26)
• Analog ramp control (actual value AQ, see Chapter
• Analog math (actual value AQ, see Chapter 4.4.30)
• PI controller (actual value AQ)
• Up/down counter (actual value Cnt, see Chapter 4.4.13)
Select the required function by the block number. For
information on parameter defaults, refer to Chapter 4.4.1.
Parameters KC, TI
Please note:
• If parameter KC has value 0, the ”P” function
(proportional control) will not be executed.
• If parameter TI has value 99:59 m, the ”I” function
(integral-action control) will not be executed.
Parameter p (number of decimals)
Applies only to the PV, SP, Min and Max values displayed in
a message text.