IDEC SmartRelay functions

IDEC SmartRelay Manual

219

Timing diagram

The nature, manner and speed with which the AQ changes

depend on the parameters KC and TI. Thus, the course of

AQ in the diagram is merely an example. A control action is

continuous; therefore the diagram portrays just an extract.

A/M

R

Dir

AQ

Mq

500 ms

Min

Max

PV

SP

/+

/–

Q

1. A disturbance causes the PV to drop, as Dir is positioned

upwards, AQ increases until PV corresponds again to

SP.

2. A disturbance causes the PV to drop, as Dir is positioned

downwards, AQ decreases until PV corresponds again to

SP.

It is not possible to change the direction (Dir) at runtime

of the function. The change is shown here for illustrative

purposes only.

3. As AQ is set to 0 by means of the input R, PV changes.

This is based on the fact that PV increases, which on

account of Dir = upwards causes AQ to drop.

Functional description

If the input A/M is set to 0, then the special function issues

output AQ with the value that you set with parameter Mq.
If the input A/M is set to 1, then automatic mode commences.

As an integral sum the value Mq is adopted, the controller

function begins the calculations.