IDEC FL1E SmartRelay User Manual
Page 233
IDEC SmartRelay functions
IDEC SmartRelay Manual
219
Timing diagram
The nature, manner and speed with which the AQ changes
depend on the parameters KC and TI. Thus, the course of
AQ in the diagram is merely an example. A control action is
continuous; therefore the diagram portrays just an extract.
A/M
R
Dir
AQ
Mq
500 ms
Min
Max
PV
SP
/+
/–
Q
1. A disturbance causes the PV to drop, as Dir is positioned
upwards, AQ increases until PV corresponds again to
SP.
2. A disturbance causes the PV to drop, as Dir is positioned
downwards, AQ decreases until PV corresponds again to
SP.
It is not possible to change the direction (Dir) at runtime
of the function. The change is shown here for illustrative
purposes only.
3. As AQ is set to 0 by means of the input R, PV changes.
This is based on the fact that PV increases, which on
account of Dir = upwards causes AQ to drop.
Functional description
If the input A/M is set to 0, then the special function issues
output AQ with the value that you set with parameter Mq.
If the input A/M is set to 1, then automatic mode commences.
As an integral sum the value Mq is adopted, the controller
function begins the calculations.