Operating Instructions Powador XP500/550-OD-TL
Page 91
U s e r i n t e r f a c e
9.1 Digital
input/output
9.1.1 Digital
input
1d
1c
2d
2c
3d
3c
4d
4c
5d
5c
1c
1c
1d
1d
2c
2c
2d
2d
UDIO
3c
3c
3d
3d
4c
4c
4d
4d
5c
5c
5d
5d
Figure 65: UDIO connection
Figure 66: UDI1 connection
Terminal number
Terminal designation
Specifi cation
Wire cross- section
1c
UDI1 P
Max 27Vdc, 27mA
AWG 20
(0.518mm
2
)
1d
UDI1 N
Table 21: Connections for digital input
The system sends digital input signal in accordance with the setting of “DI1 Select” parameter in menu of HMI
or parameter setup tool (CMT, AutoSetup).
DI1 Select
Description
Note
0
Disable DI1
1
Reserved
2
Reserved
3
Start/Stop operation of the inverter by DI1
Recognition pattern:
Stop: Δt = 1sec
Start: Δt = 2sec
Recognition pattern is checked whene-
ver DI1 input signal is at rising edge(T
0
)
then it is determined according to how
long the DI1 input signal has been
stayed in high state.
4
Start/Stop operation of the inverter by DI1
Recognition pattern:
Stop: Δt = 200msec
Start: Δt = 400msec
5
Stop operation of the inverter by DI1
Recognition pattern:
{DI1 Check Period} msec – Stop operation