Operating Instructions Powador XP500/550-OD-TL

Page 91

U s e r i n t e r f a c e

9.1 Digital

input/output

9.1.1 Digital

input

1d

1c

2d

2c

3d

3c

4d

4c

5d

5c

1c

1c

1d

1d

2c

2c

2d

2d

UDIO

3c

3c

3d

3d

4c

4c

4d

4d

5c

5c

5d

5d

Figure 65: UDIO connection

Figure 66: UDI1 connection

Terminal number

Terminal designation

Specifi cation

Wire cross- section

1c

UDI1 P

Max 27Vdc, 27mA

AWG 20

(0.518mm

2

)

1d

UDI1 N

Table 21: Connections for digital input

The system sends digital input signal in accordance with the setting of “DI1 Select” parameter in menu of HMI
or parameter setup tool (CMT, AutoSetup).

DI1 Select

Description

Note

0

Disable DI1

1

Reserved

2

Reserved

3

Start/Stop operation of the inverter by DI1

Recognition pattern:

Stop: Δt = 1sec

Start: Δt = 2sec

Recognition pattern is checked whene-

ver DI1 input signal is at rising edge(T

0

)

then it is determined according to how
long the DI1 input signal has been
stayed in high state.

4

Start/Stop operation of the inverter by DI1

Recognition pattern:

Stop: Δt = 200msec

Start: Δt = 400msec

5

Stop operation of the inverter by DI1

Recognition pattern:

{DI1 Check Period} msec – Stop operation