Operating Instructions Powador XP500/550-OD-TL

F a u l t s a n d W a r n i n g s

Fault

Code

Message

Warning Description

Possible problem and Solution(s)

1

PV Over Voltage

PV voltage exceeds the param-
eter [DC over voltage Level]

Possible problem

• The voltage of the solar generator is too
high

Solution(s)

• Check the input voltage

• Check module wiring and system

2

PV Over Current

PV current exceeds the parame-
ter [DC over current Level]

Possible problem

• The current of the solar generator is too
high

• PV system wiring short

Solution(s)

• Check the input current

• Check module wiring and system

4

CB10(PV CB) Trip

PV side circuit breaker(CB10)
tripped

Possible problem

• CB10 disconnect switch is open

• Auxiliary switch is inoperable, CB10
contactor failed closed

Solution(s)

• Check the wiring connection

• Change the CB10, replace CB10
contactor

5

PV Polarity Failure

Polarity(+, -) of PV side is
reversed

Possible problem

• Polarity of PV side is reversed
Solution(s)

• Check the wiring connection and
change if necessary

6

Ground Fault

PV side ground fault

Possible problem

• The GFDI fuse in inverter is opened
causing PV side grounding or short-cir
cuit fault(DC side Grounding Type)

• The unbalance of measured PV voltage
in inverter causing PV side grounding or
short-circuit fault(DC side Isolation
Type)

Solution(s)

• Check the solar generator for a
grounding or short-circuit fault and
Replace the GFDI Fuse(DC side
Grounding Type)

• Check the solar generator for a
grounding or short-circuit fault(DC side
Isolation Type)

Table 10: Fault