Operating Instructions Powador XP500/550-OD-TL
F a u l t s a n d W a r n i n g s
Fault
Code
Message
Warning Description
Possible problem and Solution(s)
1
PV Over Voltage
PV voltage exceeds the param-
eter [DC over voltage Level]
Possible problem
• The voltage of the solar generator is too
high
Solution(s)
• Check the input voltage
• Check module wiring and system
2
PV Over Current
PV current exceeds the parame-
ter [DC over current Level]
Possible problem
• The current of the solar generator is too
high
• PV system wiring short
Solution(s)
• Check the input current
• Check module wiring and system
4
CB10(PV CB) Trip
PV side circuit breaker(CB10)
tripped
Possible problem
• CB10 disconnect switch is open
• Auxiliary switch is inoperable, CB10
contactor failed closed
Solution(s)
• Check the wiring connection
• Change the CB10, replace CB10
contactor
5
PV Polarity Failure
Polarity(+, -) of PV side is
reversed
Possible problem
• Polarity of PV side is reversed
Solution(s)
• Check the wiring connection and
change if necessary
6
Ground Fault
PV side ground fault
Possible problem
• The GFDI fuse in inverter is opened
causing PV side grounding or short-cir
cuit fault(DC side Grounding Type)
• The unbalance of measured PV voltage
in inverter causing PV side grounding or
short-circuit fault(DC side Isolation
Type)
Solution(s)
• Check the solar generator for a
grounding or short-circuit fault and
Replace the GFDI Fuse(DC side
Grounding Type)
• Check the solar generator for a
grounding or short-circuit fault(DC side
Isolation Type)
Table 10: Fault