Operating Instructions Powador XP500/550-OD-TL

P a r a m e t e r s

The operation for FRT (Fault Ride Through) control is possible to set by parameter as follows.

Grid Under Voltage Levels

- Grid Under Voltage Level 1 – Transfer to FRT mode.

- Grid Under Voltage Level2 – Inverter stops its operation with ‘Grid Under Voltage Level 2 Fault’ when the

grid voltage below ‘Grid Under Voltage Level 2’ sustains over “Grid Under Voltage Trip Time 2”.

- Grid Under Voltage Trip Time 1 – Permissible grid voltage under ‘Grid under Voltage Level 1’ time.

- Grid Under Voltage Trip Time 2 – Permissible grid voltage under ‘Grid Under Voltage Level 2’ time.

Figure 62: FRT Parameters