Operating Instructions Powador XP500/550-OD-TL

Page 21

S t o r a g e / I n s t a l l a t i o n / S t a r t - u p

5.4 Electrical

connection

DANGER

Lethal voltages are still present in the terminals and lines of the inverter even after
the inverter has been switched off and disconnected!

Coming into contact with the lines and terminals in the inverter will cause serious
injury or death.

Only authorised electricians who are approved by the supply grid operator may open,
install and maintain the inverter.

Use extreme caution when working on the unit.

Disconnect the AC and DC sides.

Secure them against being inadvertently switched back on.

Connect the inverter only after the aforementioned steps have been taken.

5.4.1 Protective earth connection

Connect the PE bus bars

The PE (protective earth) bus bars are located on the left and right sides of the inverter cabinets.

 Connect the wires for “both” PE bus bars.

Earth the inverter

 Determine the lay-out of the permanent wiring.

 Secure the protective earths (tightening torque for PE terminals: 43Nm). Do not use plug connections.

 Check whether all connected cables are securely attached and protected from mechanical forces.

 Attach the Plexiglas cover.

Figure 13: PE busbar