2 overview of operating states – KACO Powador XP500-XP550-HV TL outdoor User Manual
Page 31
Page 32
Operating Instructions Powador XP500/550-OD-TL
S t o r a g e / I n s t a l l a t i o n / S t a r t - u p
5.6.2 Overview of operating states
Figure 20: Overview of operating states
Tag
Parameter
Default Value
T
Shift
Time Shift (Grid tab)
0sec
V
pv_start
MPPT V Start (PV Array tab)
700V
T
start
MPPT T Start (PV Array tab)
900sec
V
mpp_min
MPPT V Minimum (PV Array tab)
505V
P
stop
MPPT P Stop (PV Array tab)
7kW (above 550kVA capacity: 8kW)
T
stop
MPPT T Stop (PV Array tab)
60sec
Table 5: Parameters of operating states