F a u l t s a n d W a r n i n g s
Code
Message
Warning Description
Possible problem and Solution(s)
10
Inv. Over Voltage
Inverter side Voltage over the
parameter [Grid Over Voltage
Level 2]
Possible problem
• The inverter voltage is too high
Solution(s)
• Check the inverter voltage
• Check the inverter parameter
11
Inv. Under Voltage
Inverter side Voltage under the
parameter [Grid Under Voltage
Level 2]
Possible problem
• The inverter voltage is too low
Solution(s)
• Check the inverter voltage
• Check the inverter parameter
• Check the MC21
12
Inv. Over Frequency
Inverter side Frequency over the
parameter [Grid over Frequency
Level 2]
Possible problem
• The grid frequency is outside the
permitted range
Solution(s)
• Check the grid frequency
13
Inv. Under Frequency Inverter side Frequency under
the parameter [Grid under
Frequency Level 2]
Possible problem
• The grid frequency is outside the
permitted range
Solution(s)
• Check the grid frequency
14
Inv. Over Current
Inverter side Current over the
parameter [Inverter OverCurrent
Level]
Possible problem
• Short circuit in the IGBT
• Short circuit in the Grid
Solution(s)
• Check the grid connection
• Check the inverter connection
15
MC21(Inv. MC) Failure Inverter side contactor(MC21)
failure
Possible problem
• MC21 contactor is open
• Auxiliary switch is inoperable
Solution(s)
• Check the wiring connection
• Change the MC21
16
Inv. Phase Order
Phase order failure on the
inverter side
Possible problem
• Phase order failure on the inverter
• Wrong phase rotation
Solution(s)
• Check the wiring connection
• Reverse two phases
Table 10: Fault