Operating Instructions Powador XP500/550-OD-TL

Page 63

P a r a m e t e r s

Parameters

Min

Max

Unit

Descriptions

Power Gradient
Mode

0

5

-

Power gradient function when inverter start

0: Disable

1: Activated when connected to grid after fault
(Germany Medium Voltage Requirements)

2: Activated according to VDE-AR-N 4105
(Germany Low Voltage Requirements)

3: Activated whenever connected to grid
(Italy TERNA Grid Code)

Power Gradient
Ramp

0

600

sec

Ramp time for power gradient

Time Shift

0

6000

sec

Delay time for inverter start

Gate-way Enable

0

1

-

Reserved

Grid Level 2
Protection Enable

0

1

-

Grid level 2 protection function

0: Disable

1: Enable

Grid Over Voltage
Level 2

105

130

%

Upper limit expressed as a percentage of the rated
grid voltage for grid overvoltage level 2

Grid Under Voltage
Level 2

15

100

%

Lower limit expressed as a percentage of the rated
grid voltage for grid under voltage Level 2

Grid Under
Frequency Level 2

0

3.5

Hz

Lower limit for grid under frequency level 2

Grid Over Voltage
Level 1 Trip Time

100

10000

ms

Time for grid over voltage level 1 trip

Grid Over Voltage
Level 2 Trip Time

40

2000

ms

Time for grid over voltage level 2 trip

Grid Under Voltage
Level 1 Trip Time

100

10000

ms

Time for grid under voltage level 1 trip

Grid Under Voltage
Level 2 Trip Time

40

3000

ms

Time for grid under voltage level 2 trip

Grid Under Fre-
quency Level 1 Trip
Time

100

20000

ms

Time for grid under frequency level 1 trip

Grid Under Fre-
quency Level 2 Trip
Time

40

3000

ms

Time for grid under frequency level 2 trip

Grid Over Frequency
Level 1 Trip Time

40

3000

ms

Time for grid over frequency level 1 trip

FRT Enable

0

1

-

FRT(Fault Ride Through) Function

0: Disable

1: Enable

Table 14: Grid Parameters