KACO Powador XP500-XP550-HV TL outdoor User Manual
Page 62
Operating Instructions Powador XP500/550-OD-TL
Page 63
P a r a m e t e r s
Parameters
Min
Max
Unit
Descriptions
Power Gradient
Mode
0
5
-
Power gradient function when inverter start
0: Disable
1: Activated when connected to grid after fault
(Germany Medium Voltage Requirements)
2: Activated according to VDE-AR-N 4105
(Germany Low Voltage Requirements)
3: Activated whenever connected to grid
(Italy TERNA Grid Code)
Power Gradient
Ramp
0
600
sec
Ramp time for power gradient
Time Shift
0
6000
sec
Delay time for inverter start
Gate-way Enable
0
1
-
Reserved
Grid Level 2
Protection Enable
0
1
-
Grid level 2 protection function
0: Disable
1: Enable
Grid Over Voltage
Level 2
105
130
%
Upper limit expressed as a percentage of the rated
grid voltage for grid overvoltage level 2
Grid Under Voltage
Level 2
15
100
%
Lower limit expressed as a percentage of the rated
grid voltage for grid under voltage Level 2
Grid Under
Frequency Level 2
0
3.5
Hz
Lower limit for grid under frequency level 2
Grid Over Voltage
Level 1 Trip Time
100
10000
ms
Time for grid over voltage level 1 trip
Grid Over Voltage
Level 2 Trip Time
40
2000
ms
Time for grid over voltage level 2 trip
Grid Under Voltage
Level 1 Trip Time
100
10000
ms
Time for grid under voltage level 1 trip
Grid Under Voltage
Level 2 Trip Time
40
3000
ms
Time for grid under voltage level 2 trip
Grid Under Fre-
quency Level 1 Trip
Time
100
20000
ms
Time for grid under frequency level 1 trip
Grid Under Fre-
quency Level 2 Trip
Time
40
3000
ms
Time for grid under frequency level 2 trip
Grid Over Frequency
Level 1 Trip Time
40
3000
ms
Time for grid over frequency level 1 trip
FRT Enable
0
1
-
FRT(Fault Ride Through) Function
0: Disable
1: Enable
Table 14: Grid Parameters