1 operating dc voltage range – KACO Powador XP500-XP550-HV TL outdoor User Manual
Page 60
Operating Instructions Powador XP500/550-OD-TL
Page 61
P a r a m e t e r s
Parameters
Min
Max
Unit
Descriptions
MPPT V Minimum
200
800
V
dc
Minimum voltage to run MPPT
Exception)
DC Over Voltage
Level
300
1020
V
dc
Upper limit for PV over voltage fault
DC Over Current
Level
0
150
%
Upper limit for PV over current fault
MPP Factor
0
1
-
Maximum power point factor
MPP Range Upper
10
300
V
dc
Upper limit of maximum power point
MPP Range Lower
10
300
V
dc
Lower limit of maximum power point
PV Operation Level
900
1020
V
dc
Maximum PV operation level
Table 12: PV Array Parameters
8.1.1
Operating DC voltage range
Figure 39: Operating DC voltage range
The range of possible operational input voltage is from [MPPT V Minimum] to [PV Operation Level]. The picture
above shows that the output power decreases linearly where the input power is from [MPPT V Maximum] to
[PV Operation Level].