Operating Instructions Powador XP500/550-OD-TL

Page 65

P a r a m e t e r s

Parameters

Min

Max

Unit

Descriptions

Reconnection
Condition Check
Time Normal

0

1800

sec

This parameter is used for time check during
“Reconnection condition” for all the time except
after fault.

Reconnection
Condition Check
Time After Fault

0

1800

sec

This parameter is used for time check during
“Reconnection condition” for after fault only.

Grid Over Frequency
Level 3

0

3

Hz

Upper limit for grid over frequency level 3

Grid Over Frequency
Level 3 Trip Time

40

2000

ms

Time for grid over frequency Level 3 trip

Grid Over Voltage
Level Slow

105

115

%

This parameter represents Upper limit for the
average RMS value of grid voltage as a percentage
of the rated grid voltage.

If the average RMS value of grid voltage exceeds
this parameter setting, fault will be occurred.

VDE-AR-N 4105(Germany Low Voltage Require-
ments)

Grid Over Voltage
Level Slow Shift
Average Time

-1

3000

sec

This parameter determines how long the average
RMS value of grid voltage will be calculated.
(Low Voltage Requirements: 600 seconds duration)

Negative value means that the relevant function
(Grid Over Voltage level slow) is disabled.

Reconnection
Condition Warning
Delay

0

600

sec

Time delay for Reconnection Condition Warning

Grid Under Fre-
quency Level 3

0

3

Hz

Lower limit for grid over frequency level 3

Grid Under Fre-
quency Level 3 Trip
Time

0

60000

ms

Time for grid over frequency Level 3 trip

Upper Deadband
PPN

100

110

%

Voltage Level for activation of P/Pn function when
selected CEI 0-21 grid code

Lower Deadband
PPN

90

100

%

Voltage Level for deactivation of P/Pn function
when selected CEI 0-21 grid code

Upper Deadband
QV

10

100

%

Active Power Level for activation of Q(V) function
when selected CEI 0-21 grid code

Lower Deadband
QV

1

20

%

Active Power Level for deactivation of Q(V)
function when selected CEI 0-21 grid code

QV Voltage 1

100

110

%

Voltage upper dead band of Q(V) function when
selected CEI 0-21 grid code

QV Voltage 2

90

100

%

Voltage lower dead band of Q(V) function when
selected CEI 0-21 grid code

Table 14: Grid Parameters