beautypg.com

1 frt enable off – KACO Powador XP500-XP550-HV TL outdoor User Manual

Page 65

background image

Page 66

Operating Instructions Powador XP500/550-OD-TL

P a r a m e t e r s

Parameters

Min

Max

Unit

Descriptions

QV Voltage 3

100

110

%

Voltage upper level to calculate ramp of Q(V)
function when selected CEI 0-21 grid code

QV Voltage 4

90

100

%

Voltage lower level to calculate ramp of Q(V)
function when selected CEI 0-21 grid code

QV Inductive Max

0

48

%

Reactive Power inductive maximum value of Q(V)
function

QV Capacitive Max

0

48

%

Reactive Power capacitive maximum value of Q(V)
function

Table 14: Grid Parameters

8.3.1 FRT Enable Off

If the function of FRT(Fault-ride through) is not active, XP series parameters for abnormal grid is as follows.

Grid Under Frequency

Figure 40: Grid under frequency

1. f < f

rated

–2Hz, t > 10s

 Grid Under Frequency Level 1 Fault

2. f < f

rated

–2.5Hz, t > 100ms

 Grid Under Frequency Level 2 Fault