3 unit description, 1 technical data – KACO Powador XP500-XP550-HV TL outdoor User Manual
Page 8
Operating Instructions Powador XP500/550-OD-TL
Page 9
U n i t D e s c r i p t i o n
3 Unit
Description
3.1 Technical
Data
Model
XP500-OD-TL
XP550-OD-TL
DC Input
PV Max. generator Power
600kW
660kW
MPP range
550V ~ 830V
Max. permissible DC voltage
1100V
1*
Max. permissible DC current
1091A
1200A
Voltage ripple
< 3%
Current ripple
< 4%
Number of DC inputs
6
AC Output
Rated power
500kVA
550kVA
Grid voltage
3*370V (±10%)
Rated current
780A
858A
Grid frequency
50Hz / 60Hz
THD of grid current
< 3% at rated power
Power factor (cos θ)
≥ 0.99 at rated power
0.8 leading … 0.8 lagging (Adjustable)
Power Consumption
Internal consumption in operation
< 1% of rated power (< 1650W)
Internal consumption in stand-by
< Approx. 110W
Effi ciency
Max. effi ciency
98.7%
98.7%
Euro effi ciency
98.3%
98.3% (Expectation)
Environment
Operating temperature range
-20°C ~ +50°C
Storage temperature range
-20°C ~ +70°C
Relative humidity
0 ~ 100% (condensing)
Max. altitude above mean sea level
2000m (as per IEC 62040/3)
Cooling
Forced Fan (6940m
3
per hour)
Audible noise
< 70dB
Protection class
IP54
Table 1: Electrical data of the inverter
1*
1100V
dc
is no-load voltage. And max. operating voltage is 1000V
dc