Operating Instructions Powador XP500/550-OD-TL
F a u l t s a n d W a r n i n g s
Message
Code
Description
CAN EP Failure
137
CAN bus communication Error-Passive error
CAN Bus-Off
138
CAN bus communication Bus-off error
CAN Wrong Message
139
Reception of Wrong message in CAN bus communication
CAN Time Out
140
Time out in CAN bus communication
CAN Multiple Master
141
There are multiple Masters in CAN bus communication
Table 7: Warning
6.2 Fault
Message
Code
Description
PV Over Voltage
1
PV voltage exceeds the parameter [DC over voltage Level]
PV Over Current
2
PV current exceeds the parameter [DC over current Level]
CB10(PV CB) Trip
4
PV side circuit breaker(CB10) tripped
PV Polarity Failure
5
Polarity(+, -) of PV side is reversed
Ground Fault
6
PV side ground fault
Inv. Over Voltage
10
Inverter side Voltage over the parameter [Grid Over Voltage Level 2]
Inv. Under Voltage
11
Inverter side Voltage under the parameter [Grid Under Voltage Level 2]
Inv. Over Frequency
12
Inverter side Frequency over the parameter [Grid over Frequency Level 2]
Inv. Under Frequency
13
Inverter side Frequency under the parameter [Grid under Frequency
Level 2]
Inv. Over Current
14
Inverter side Current over the parameter [Inverter OverCurrent Level]
MC21(Inv. MC) Failure
15
Inverter side contactor(MC21) failure
Inv. Phase Order
16
Phase order failure on the inverter side, wrong phase rotation
Inductor or TR Over Temp.
18
Inductor or Transformer temperature over 150°C
Inv. Current Unbalance
19
The unbalanced current of inverter side
PEBB(1) IGBT Fault
20
PEBB 1 IGBT failure
PEBB(2) IGBT Fault
21
PEBB 2 IGBT failure
PEBB(3) IGBT Fault
22
PEBB 3 IGBT failure
PEBB Over Temp. Analog
24
The temperature of the heat-sink over the parameter [Heatsink OT
Level] (Analog)
PEBB Over Temp. Digital
25
The temperature of the heat-sink over 100°C(Digital)
Grid Over Voltage 1
30
Grid side Voltage over the parameter [Grid Over Voltage Level 1]
Grid Under Voltage 1
31
Grid side Voltage under the parameter [Grid Under Voltage Level 1]
Table 8: Fault