Operating Instructions Powador XP500/550-OD-TL

P a r a m e t e r s

Grid Over Voltage

Figure 43: Grid over voltage

1. U > 1.1*U

rated

, t > 5s

 Grid Over Voltage Level 1 Fault

2. U > 1.2*U

rated

, t > 100ms

 Grid Over Voltage Level 2 Fault

8.3.2 FRT Enable On

The parameter when FRT Enable is on is as follows.

Parameters

Min

Max

Unit

Descriptions

FRT Enable

0

1

-

FRT(Fault Ride Through) Function

0: Disable

1: Enable

Grid Under Voltage
Level 2

15

100

%

Lower limit expressed as a percentage of the
rated grid voltage for grid under voltage Level 2

Grid Under Voltage
Level 1 Trip Time

100

10000

ms

Time for grid under voltage level 1 trip

Grid Under Voltage
Level 2 Trip Time

40

3000

ms

Time for grid under voltage level 2 trip

MPP Range Upper

10

300

V

dc

Upper limit of maximum power point

MPP Range Lower

10

300

V

dc

Lower limit of maximum power point

Table 15: FRT Enable On