beautypg.com

3 solution for error code – KACO Powador XP500-XP550-HV TL outdoor User Manual

Page 45

background image

Page 46

Operating Instructions Powador XP500/550-OD-TL

F a u l t s a n d W a r n i n g s

6.3

Solution for Error code

The Inverter can detect faults during operation. The inverter will display the fault in the CMT. Faults are indi-
cated in the CMT with an error code, and a plain text message with the error code and system plant name in
the text line will be sent to the system operator (only available if purchased and confi gured during setup). This
section describes how to recognize the types of faults and how to correct these faults.

Warning

Code Message

Warning

description

Possible problem and Solution(s)

81

SP1(PV SP) Failure

Failure of the PV side surge
protector(SP1)

Possible problem

• Lightning strike on or near the PV system
wiring

Solution(s)

• Visual inspection

• Change the SPD

83

PV Fuse Failure

PV side Fuse failure(option)

Possible problem

• PV system wiring short

• Short circuit in the IGBT

Solution(s)

• Check the input current

• Check module wiring

• Change the FUSE

100

PEBB Over Temp.
Warning

The temperature of the
PEBB(Power Electronics Building
Block) over 85°C(185°F)

Possible problem

• PEBB Fan Failure

Solution(s)

• Clean the fi lters or PEBB heat-sink fi ns

• Change the PEBB Fan

101

PEBB Fan Failure

Failure of a PEBB(Power Elec-
tronics Building Block) fan

Possible problem

• PEBB Fan Failure

Solution(s)

• Change the PEBB Fan

110

SP2(Grid SP) Failure

Failure of the grid side surge
protector(SP2)

Possible problem

• Lightning strike on or near the grid
system wiring

Solution(s)

• Visual inspection

• Change the SPD

120

Test Mode

The system is working in test
mode

Possible problem

• The system is working in test mode

Solution(s)

• Change the parameters in the GUI

Table 9: Warning