8 parameters, 1 pv array parameters – KACO Powador XP500-XP550-HV TL outdoor User Manual

Page 59

background image

Page 60

Operating Instructions Powador XP500/550-OD-TL

P a r a m e t e r s

8 Parameters

The KACO XP-HV and XP-TL series parameters are pre-confi gured for operation. It is a good idea to adapt a
number of the KACO XP series parameters to the solar generator.

XP500/550-OD-TL parameters are subdivided into ten:

PV

Array

Setting values for MPPT control and startup of inverter

Inverter

Setting values for inverter rate and cabinet temperature

Grid

Setting values for abnormal and rated levels of grid

Time

Setting values for the current time

Digital

Setting values for digital interface

Analog

Setting values for analog interface

Controller

Setting values for inverter control

Trace

Setting values for inverter fault analysis

Offset

Setting values for sensing offset calibration

Gain

Setting values for sensing gain calibration

8.1

PV Array Parameters

Parameters

Min

Max

Unit

Descriptions

MPPT Enable

0

1

-

1: MPPT is enabled

0: MPPT is disabled

MPPT V Maximum

0

830

V

dc

Maximum voltage to run MPPT

MPPT V Start

200

800

V

dc

MPPT wake-up voltage

MPPT T Start

0

3600

sec

Time delay for MPPT wake-up

MPPT P Stop

0

10000

W

Disconnect inverter from Grid when PV output
power is lower than the setting value of {MPPT P
Stop}.

MPPT T Stop

0

600

sec

Time delay while inverter decides if PV output
power is lower than the setting value of {MPPT P
Stop}.

Table 12: PV Array Parameters