F a u l t s a n d W a r n i n g s

Code

Message

Warning Description

Possible problem and Solution(s)

18

Inductor or TR Over
Temp

Inductor or Transformer temper-
ature over 150°C

Possible problem

• Cabinet fan failure
Solution(s)

• Cleaning the fi lters

• Change the cabinet Fan

20

PEBB(1) IGBT Fault

PEBB IGBT U failure

Possible problem

• Short circuit in the IGBT

Solution(s)

• Visual inspection

• Change the PEBB

21

PEBB(2) IGBT Fault

PEBB IGBT V failure

22

PEBB(3) IGBT Fault

PEBB IGBT W failure

24

PEBB Over Temp.
Analog

The temperature of the heat-
sink over the parameter [Heat-
sink OT Level] (Analog)

Possible problem

• PEBB fan failure

Solution(s)

• Clean the fi lters

• Inspect and if necessary clean the
heat-sink fi ns

• Change the PEBB Fan

25

PEBB Over Temp.
Digital

The temperature of the heat-
sink over 100°C(Digital)

Possible problem

• PEBB Fan Failure

Solution(s)

• Inspect and if necessary clean the
heat-sink fi ns Change the PEBB Fan

30

Grid Over Voltage
level 1

Grid side Voltage over the
parameter [Grid Over Voltage
Level 1]

Possible problem

• The grid voltage is too high

Solution(s)

• Check the grid voltage

• Check the grid parameter

31

Grid Under Voltage
level 1

Grid side Voltage under the
parameter [Grid Under Voltage
Level 1]

Possible problem

• The grid voltage is too low

Solution(s)

• Check the grid voltage

• Check the grid parameter

• Check the MCB24

32

Grid Over Frequency
level 1

Grid side Frequency over the
parameter [Grid Over Frequency
Level 1]

Possible problem

• The grid frequency is outside the
permitted rang

Solution(s)

• Check the grid frequency

• Check the grid parameter