beautypg.com

KACO Powador XP500-XP550-HV TL outdoor User Manual

Page 73

background image

Page 74

Operating Instructions Powador XP500/550-OD-TL

P a r a m e t e r s

Parameters

Min

Max

Unit

Parameters

Cabinet FAN PWM

0

100

-

Reserved

Remote Power
Control Ramp

0

600

sec

The slope of inverter output active poser when
remote power is controlled

Total Yield

0

99999999

kWh

Check total yield of generation(Read only)

Today Yield

0

99999999

kWh

Check day yield of generation(Read only)

CTRL_RSV1

0

999.99

-

Reserved

CTRL_RSV2

0

999.99

-

Reserved

CTRL_RSV3

0

999.99

-

Reserved

CTRL_RSV4

0

999.99

-

Reserved

Anti-Islanding
Enable

0

1

-

The use of anti-islanding controller, Yes(1) NO(0)

APS Line Deadband 0

999.99

-

The setup value for anti-islanding control

Reactive Power
Limit

0

999.99

-

The setup value for anti-islanding control

Wind Speed

0

9999.9

-

Reserved

Power Derating
Enable

0

1

-

The use of power decline controller according to
PEBB temperature, Yes(1) NO(0)

Power Derating
Enable Temperature

50

100

-

Temperature level which starts decreasing power
according to PEBB temperature

Power Derating
Disable Temperature

40

90

-

Temperature level which stops decreasing power
according to PEBB temperature

Power Derating
Reference Tempera-
ture

45

95

-

PEBB temperature reference value

Power Derating P
Gain

0

10

-

Power declining controller’s P gain according to
PEBB temperature

Grid IIR Filter Cutoff
Frequency

0

10

Hz

Filter cutoff frequency used for RMS value detec-
tion of grid voltage

Asynchronous Fault
Count

0

100

-

Reserved

Asynchronous Fault
Enable

0

1

-

Reserved

Grid Positive
Sequence

0

999.9

V

Positive sequence value of grid

Table 19: Controller Parameters