2 inverter parameters, 3 grid parameters – KACO Powador XP500-XP550-HV TL outdoor User Manual
Page 61
Page 62
Operating Instructions Powador XP500/550-OD-TL
P a r a m e t e r s
8.2 Inverter
Parameters
Parameters
Min
Max
Unit
Descriptions
Transformer & Type 0
8
N/A
This parameter determines device specifi c informa-
tion such as a switch type on DC side and whether
the inverter has an internal transformer.
Inverter Capacity
100
550
kW
Power Capacity of the inverter
Inverter Over
Current Level
0
200
%
Upper limit for inverter over current fault
Current Limit
0
150
%
Limit of current which produces from the inverter
Cabinet Tempera-
ture Maximum
30
70
°C
Upper limit for cabinet over temperature warning
Cabinet Tempera-
ture Minimum
-25
10
°C
Lower limit for cabinet under temperature warning
PEBB Temperature
Unbalance Level
5
30
°C
Limit of Temperature gap between PEBBs
Table 13: Inverter Parameters
8.3 Grid
Parameters
Parameters
Min
Max
Unit
Descriptions
Rated Grid Voltage
208
400
V
Rated value of the grid voltage
Rated Grid
Frequency
50
60
Hz
Rated value of the grid frequency
Grid Over Voltage
Level 1
105
130
%
Upper limit expressed as a percentage of the rated
grid voltage for grid overvoltage level 1
Grid Under Voltage
Level 1
75
100
%
Lower limit expressed as a percentage of the rated
grid voltage for grid under voltage Level 1
Grid Over Frequency
Level 1
0
3
Hz
Upper limit for grid over frequency level 1
Grid Under Fre-
quency Level 1
0
3
Hz
Lower limit for grid under frequency level 1
Frequency Depend-
ant Power Reduc-
tion Mode
0
2
-
Power reduction function dependant on frequency
rise
0: Disable
1: Enable
Table 14: Grid Parameters