Page 78

Operating Instructions Powador XP500/550-OD-TL

P a r a m e t e r s

Figure 50: State Machine

Power derating is enabled or disabled by an output of state machine which is decided by 4 inputs. And while
the output of state machine is 1, a decreasing rate affects an output power.

A decreasing rate is calculated by multiplying factor K({Power Derating P Gain}) and a difference between refer-
ence temperature({Power Derating Reference Temperature}) and PEBB heatsink temperature}.

An output of state machine depends on the state in which state machine is running. A transfer between states
happens when defi ned conditions are satisfi ed. Basically, if {Power Derating Enable} is 0, the state is “Disable”.
And If {Power Derating Enable} is 1, transfer is done according to PEBB heatsink temperature.

Following examples show power derating by default parameter.

Descriptions for sections of Example of Power Derating are:

T1: Inverter produces energy and PEBB temperature rises.

T2: When PEBB temperature is higher than 90°C, power derating is activated. And inverter controls output
power according to expression, P(%) =

100

-(

T

PEBB

-80)x2 until power derating is deactivated.

T3: Output power decrease and PEBB temperature drops. When PEBB temperature is lower than 70°C, power
derating is deactivated. And inverter doesn’t decrease output power.