8.7 Controller
Parameters
Parameters
Min
Max
Unit
Parameters
VC P Gain
0
999.99
N/A
PV voltage controller’s P Gain
VC I Gain
0
999.99
N/A
PV voltage controller’s I Gain
Voltage Detection
LPF
0
9999
Hz
Grid Voltage and Inverter voltage fi lter of dq axis
CC P Gain
0
999.99
N/A
Inverter output current controller’s P Gain
CC I Gain
0
999.99
N/A
Inverter output current controller’s I Gain
CC di/dt
1
9999
p.u.
Slope of inverter rated current generation
Ramp
0
99999
msec
Slope of PV voltage generation(time for 100V
change)
Li
0
99999
uH
Inductance value of inverter output LC fi lter
Vdc Reference
0
999.9
Vdc
DC voltage reference when it is not in MPPT range
CC Period
100
400
usec
Inverter switching frequency
PLL P Gain
0
999.99
N/A
Grid voltage PLL’s P Gain
PLL I Gain
0
999.99
N/A
Grid voltage PLL’s I Gain
Auto Fault Reset
Count
0
20
times
The maximum count of auto reset function
Heatsink OT Level
50
150
°C
The maximum value of PEBB temperature
Power Compensa-
tion
0
1
-
Power compensation for MPPT control
Test mode
0
99999
N/A
The value for function test mode
Options
0
99999
N/A
Outside option board setup
Deviation Tolerance
Time
1
25
20msec
Level 1 trip time use when level 2 protection
disable
Reactive Power
-30
30
%
The control value for reactive power degree of
accuracy
Variable MPP Vmin
Enb
0
1
-
The setup value for inverter operation rage
maximization
T_CLOUD
0
3600
sec
Time for declines of PV generation due to cloud
T_CLOUD_CNT
0
20
times
Count for declines of PV generation due to cloud
Remote Power
Control
0
100
%
Inverter active power which can be controlled
from outside device
PEBB2 Temperature 0
150
°C
PEBB2 temperature(Read only)
PEBB3 Temperature 0
150
°C
PEBB3 temperature(Read only)
Current Unbalance
Limit
0
100
%
Unbalanced current level
Table 19: Controller Parameters