1 message send function, 1 outline specifications – Yaskawa JAPMC-MC2303-E User Manual
Page 87
6.1 Message Send Function
6.1.1 Outline Specifications
6-2
6.1 Message Send Function
When a request is sent assuming that the 262IF-01 is a client for FL-net message transmission or a response is sent
assuming that it is a server, the message send function “MSG-SND” is used.
When no response comes from remote device, retransmission is performed in the 262IF-01 according to the FL-net
protocol. When a timeout is detected in the 262IF-01, the MSG-SND function is terminated abnormally.
A timeout is detected when no response comes in spite three attempts (each involving a waiting time of 100 ms)
made to receive ACK after sending message.
6.1.1 Outline Specifications
∗ 1. The I/O designations are as follows:
B-VAL: I/O is specified as bit data.
I-REG: I/O is specified as integer data. Specify the number of an integer register.
Constants (immediate data) can also be specified for inputs.
Address input: The address of the specified register (any integer register) is passed to the function.
∗ 2. Non-procedure 1: Data is sent in word units.
Function Name
MSG-SND
Function
Sends a message to a remote station on the line specified by the Transmission Device Type parameter
(DEV-TYP). The function supports multiple protocols. The Execute command must be held ON until
the Complete or Error output turns ON.
Function Definition
I/O Definitions
No.
Name
I/O Designation
*1
Description
Inputs
1
Execute
B-VAL
Send Message command
2
Abort
B-VAL
Send Message Abort command
3
Dev-Typ
I-REG
Transmission Device Type
FL-net = 14
4
Pro-Typ
I-REG
Communication Protocol
MEMOBUS = 1, Non-procedure 1
*2
= 2
5
Cir-No
I-REG
Circuit Number
FL-net = 1 to 8
6
Ch-No
I-REG
Transmission Buffer Channel Number
FL-net = 1 to 10
7
Param
Address input
Parameter List Leading Address
(MA, DA)
Outputs
8
Busy
B-VAL
Processing in progress.
9
Complete
B-VAL
Processing completed.
10
Error
B-VAL
Error has occurred.