2.1 Overview of 262IF-01 Module
2.1.1 Module Specifications
2-4
∗ 1. The cable length restriction in repeater (repeater hub or switching hub) usage varies depending on a selected
baud rate.
For repeater or switching hubs, use a commercially available hub for Ethernet. Hubs manufactured by the Japan
Electrical Manufacturer’s Association (JEMA) are recommended.
• Restrictions on 100BASE-TX connection
• Restrictions on 10BASE-T connection
∗ 2. The I/O assignment restriction, which defines that the maximum number of nodes as 64 nodes including the self-
node, is based on MP Series Machine Controller specifications.
∗ 3. A message can be only sent from the client. (Client: Data sending side, Server: Data receiving side)
Cyclic
Transmission
Specifications
Number of Nodes
Up to 254 nodes (at repeater usage)
(262IF-01 I/O can be assigned to 64 nodes only including the self-node.)
*2
Maximum Data Size
Within network:
Area 1 (bit data): 8 kbits
Area 2 (word data): 8 kwords
Per station:
Area 1 + area 2: Area allocation is allowed up to 8 kbits + 8 kwords.
Data Exchange
N : N
Message
Transmission
Specifications
Number of Message
Channels
10
Engineering
Communication
Not supported
Message Service
Word block read, word block write, network parameter read, network parameter
write
*3
, stop command
*3
, start command
*3
,
profile read, transparent message, log data read, log data clear, message loopback
Number of Transmission
Words
Up to 512 words
(cont’d)
Item
Specifications
Item
When Repeater Hub Is
Connected
When Switching Hub Is
Connected
Cable length between node and
hub
100 m or less
100 m or less
Cable length between hubs
5 m or less
100 m or less
Number of hubs between nodes
Up to 2 hubs
Not limited
Item
When Repeater Hub Is
Connected
When Switching Hub Is
Connected
Cable length between node and
hub
100 m or less
100 m or less
Cable length between hubs
100 m or less
100 m or less
Number of hubs between nodes
Up to 4 hubs
Not limited