beautypg.com

5 status tab page – Yaskawa JAPMC-MC2303-E User Manual

Page 65

background image

4.2 FL-net Transmission Definition

4.2.5 Status Tab Page

4-12

4.2.5 Status Tab Page

The FL-net status can be monitored on the Status Tab Page.
The display contents are updated as needed.

The following gives a detailed description.

Status of local node

Displays the local node status in the lower-place two digits of a four-digit hexadecimal number.

Bit 0 to 2: Reserved (Not used. Always set to 0.)
Bit 3: Token monitoring time error (1: End of time period set in token monitoring timer, 0: Normal)
Bit 4: Common memory setting range error (1: Error, 0: Normal)
Bit 5: Frame waiting status (1: Wait for frame reception from other node, 0: Frame wait reset)
Bit 6: Duplicated node number detection (1: Duplicated number detected, 0: Normal)
Bit 7: Joined to network (1: Joined, 0: Not joined)
Bit 8 to Bit F: Reserved (Not used. Always set to 0.)

Minimum permissible frame interval

Displays the minimum permissible frame interval set on the Transmission Parameters Tab page. (Unit: ms)

Refresh cycle measuring time

Displays the refresh cycle time measurement value (current value). (Unit: ms)

Refresh cycle time (max.)

Displays the maximum refresh cycle time. (Unit: ms)

Refresh cycle time (min.)

Displays the minimum refresh cycle time. (Unit: ms)

Token monitoring time

Displays the token monitoring time set on the Transmission Parameters Tab Page. (Unit: ms)

Vendor code

Displays the vendor name “YASKAWA.”

Manufacturer model name

Displays the first ten bytes, “JAPMC-CM23,” of “JAMPMC-CM2303-E” in the 262IF-01 model number.