5 status tab page – Yaskawa JAPMC-MC2303-E User Manual
Page 65
![background image](https://www.manualsdir.com/files/819956/content/doc065.png)
4.2 FL-net Transmission Definition
4.2.5 Status Tab Page
4-12
4.2.5 Status Tab Page
The FL-net status can be monitored on the Status Tab Page.
The display contents are updated as needed.
The following gives a detailed description.
Status of local node
Displays the local node status in the lower-place two digits of a four-digit hexadecimal number.
Bit 0 to 2: Reserved (Not used. Always set to 0.)
Bit 3: Token monitoring time error (1: End of time period set in token monitoring timer, 0: Normal)
Bit 4: Common memory setting range error (1: Error, 0: Normal)
Bit 5: Frame waiting status (1: Wait for frame reception from other node, 0: Frame wait reset)
Bit 6: Duplicated node number detection (1: Duplicated number detected, 0: Normal)
Bit 7: Joined to network (1: Joined, 0: Not joined)
Bit 8 to Bit F: Reserved (Not used. Always set to 0.)
Minimum permissible frame interval
Displays the minimum permissible frame interval set on the Transmission Parameters Tab page. (Unit: ms)
Refresh cycle measuring time
Displays the refresh cycle time measurement value (current value). (Unit: ms)
Refresh cycle time (max.)
Displays the maximum refresh cycle time. (Unit: ms)
Refresh cycle time (min.)
Displays the minimum refresh cycle time. (Unit: ms)
Token monitoring time
Displays the token monitoring time set on the Transmission Parameters Tab Page. (Unit: ms)
Vendor code
Displays the vendor name “YASKAWA.”
Manufacturer model name
Displays the first ten bytes, “JAPMC-CM23,” of “JAMPMC-CM2303-E” in the 262IF-01 model number.