3 ) programming example – Yaskawa JAPMC-MC2303-E User Manual
Page 119
6.5 Programming Example
6.5.1 Word Block Data Read (Client)
6-34
( 3 ) Programming Example
The following shows an example of ladder programming executed by the settings in the previous page.
IF
SB000003==true
0000
0000
NL-1
STORE
Source 00001
Dest
DW00002
0001
0001
NL-2
STORE
Source 00009
Dest
DW00004
0002
0002
NL-2
STORE
Source 00000
Dest
DW00005
0003
0003
NL-2
STORE
Source 000512
Dest
DW00006
0004
0004
NL-2
STORE
Source 00000
Dest
DW00007
0005
0005
NL-2
STORE
Source 00000
Dest
DW00008
0006
0006
NL-2
STORE
Source 00000
Dest
DW00009
0007
0007
NL-2
STORE
Source 00000
Dest
DW00010
0008
0008
NL-2
STORE
Source 00000
Dest
DW00011
0009
0009
NL-2
STORE
Source 00000
Dest
DW00012
0010
0010
NL-2
STORE
Source 00000
Dest
DW00024
0011
0011
NL-2
STORE
Source 00000
Dest
DW00025
0012
0012
NL-2
END_IF
0013
0013
NL-1
One scan at startup
Sets parameters in the first scan after startup.
(Low-speed scan (DWG.L): SB000003,
High-speed scan (DWG.H): SB000001)
Sets the coil offset.
Sets the input relay offset.
Sets the input register offset.
Sets the holding register offset.
Clears the system registers.
Clears the normal pass counter.
Clears the error counter.
Sets the remote node number.
Sets the function code (word block read).
Sets the data address (address 0).
Sets the data size (512 words).
Sets the remote CPU number.