2 word block data write (client), 1 ) msg-snd function setting, 2 ) parameter setting – Yaskawa JAPMC-MC2303-E User Manual
Page 121
6.5 Programming Example
6.5.2 Word Block Data Write (Client)
6-36
6.5.2 Word Block Data Write (Client)
The following shows an example where the 262IF-01 acts as an FL-net message client to request a word block data
write with a data size of 100 words from a virtual address offset 0 to the remote device (node number 254).
( 1 ) MSG-SND Function Setting
The MSG-SND function is set as follows:
( 2 ) Parameter Setting
The parameter list from DA00000 is set as follows:
For register access method and notes at register input, refer to 6.4 Displaying a Register List and Notes at Register
Input on page 6-30.
When the Execute (DB000201) is set to ON (=1) from the above settings, the 262IF-01 sends a word block data write
request (transaction code: 65006).
Data of MW00000 to MW000511 (512 words) is read and written in the virtual address of a remote device for data size
of 512 words from offset 0.
When a word block data response (transaction code: 65206) is received from a remote device, COMPLETE in the
MSG-SND function goes ON for one scan.
For transaction codes, refer to 6.1.5 ( 5 ) PARAM05: Data Address on page 6-13.
Transmission device = FL-net
Protocol type = MEMOBUS
Circuit number = 1
Transmission buffer channel number = 1
Parameter list leading address
= DA00000
(DW00000 to DW00016 is used.)
Parameter list
F
· · · · · · ·
0
Register
Contents
Setting
Value
Remarks
PARAM00
DW00000
Processing result
–
PARAM01
DW00001
Status
–
PARAM02
DW00002
Remote node number
1
PARAM03
DW00003
Option
0
Not used
PARAM04
DW00004
Function code
0Bh
Word block data write
PARAM05
DW00005
Data address
0
FL-net virtual address
PARAM06
DW00006
Data size
512
PARAM07
DW00007
Remote CPU number
(Address upper word)
0
PARAM08
DW00008
Coil offset
0
Not used
PARAM09
DW00009
Input relay offset
0
Not used
PARAM10
DW00010
Input register offset
0
Not used
PARAM11
DW00011
Holding register offset
0
PARAM12
DW00012
Reserved by the system
0
PARAM13
DW00013
Reserved by the system
0
PARAM14
DW00014
Reserved by the system
0
PARAM15
DW00015
Reserved by the system
0
PARAM16
DW00016
Reserved by the system
0