12 (2) warning display and troubleshooting – Yaskawa Sigma II Series DC Power Input SGMAJ User Manual
Page 293

10 Inspection, Maintenance, and Troubleshooting
10.1.3 Troubleshooting of Alarm and Warning
10-12
(2) Warning Display and Troubleshooting
Table 10.4 Warning Display and Troubleshooting
Warning
Display
Warning Name
Situation at Warning
Occurrence
Cause
Corrective Actions
A.91
Overload:
Warning for the 
alarms A71 and 
A72
In either of the fol-
lowing cases:
1. 20% of the over-
load detection level 
of A71
2. 20% of the over-
load detection level 
of A72.
Occurs when the servo 
was ON.
Wiring is incorrect and the contact in servomotor 
wiring is faulty.
Correct the servomotor wiring.
Wiring is incorrect and the contact in encoder 
wiring is faulty.
Correct the encoder wiring.
A SERVOPACK fault occurred.
Replace the SERVOPACK.
The servomotor did not 
run with a reference 
input.
Servomotor wiring is incorrect and the contact is 
faulty.
Correct the servomotor wiring.
Encoder wiring is incorrect and the contact is 
faulty.
Correct the encoder wiring.
The starting torque exceeds the maximum torque.
Reconsider the load and operation condi-
tions. Or, check the servomotor capacity.
A SERVOPACK fault occurred.
Replace the SERVOPACK.
Occurred during nor-
mal operation.
The effective torque exceeds the rated torque.
Reconsider the load and operation condi-
tions. Or, check the servomotor capacity.
Temperature in the SERVOPACK panel is high.
Reduce the in-panel temperature to 55
°C
or less.
A SERVOPACK fault occurred.
Replace the SERVOPACK.
A.93
Absolute Encoder 
Battery Warning
(The battery voltage 
stays below the 
specified value 4 
seconds after the 
control power sup-
ply was turned ON.)
(Only when an 
absolute encoder is 
connected.)
Occurred when the con-
trol power supply was 
turned ON
(Setting: Pn002.2=1).
A SERVOPACK board fault occurred. (The abso-
lute encoder is used in the incremental encoder 
setting.)
Replace the SERVOPACK.
Occurred 4 seconds or 
more after the control 
power supply was 
turned ON
(Setting: Pn002.2=0).
When an absolute 
encoder was used.
The battery connection is incorrect or faulty.
Connect correctly the battery.
The battery voltage is lower than the specified 
value 2.7 V.
Replace the battery, and turn OFF the 
encoder power supply and ON again.
A SERVOPACK board fault occurred.
Replace the SERVOPACK.