HzRtg
Nominal frequency of the power distribution grid 40 Hz … 62 Hz
50 Hz
HzCtlhhLim
Threshold value for overfrequency in level 2
50 Hz … 70 Hz
55 Hz
HzCtlhhLimTm
Tripping time for overfrequency in level 2
0 s … 5 s
0.1 s
HzCtlhLim
Threshold value for overfrequency in level 1
50 Hz … 70 Hz
51.5 Hz
HzCtlhLimTm
Tripping time for overfrequency in level 1
0 s … 5 s
0.1s
HzCtllLim
Threshold value for underfrequency level 1
40 Hz … 60 Hz
47.5 Hz
HzCtllLimTm
Tripping time for underfrequency in level 1
0 s … 600 s
0.1 s
HzCtlllLim
Threshold value for underfrequency in level 2
40 Hz … 60 Hz
46 Hz
HzCtlllLimTm
Tripping time for underfrequency level 2
0 s … 600 s
0.1 s
HzCtlMin
Threshold value for underfrequency level 3
40 Hz … 60 Hz
44 Hz
HzCtlMinTm
Tripping time for underfrequency level 3
0 s … 600 s
0.1 s
Name
Description
Value / range Default
value
GriGrdMonTm Time span in which the activation conditions must
be satisfied so that the power distribution grid can
be switched.
0 ms … 600 ms
5 s
VCtlOpMinNom Minimum grid voltage for switching on the power
distribution grid. The parameter is based on the
nominal voltage "VRtg".
0% … 100%
95%
VCtlOpMaxNom Maximum grid voltage for switching on the power
distribution grid. The parameter is based on the
nominal voltage "VRtg".
100% … 200%
115%
HzCtlOpMin
Minimum power frequency for switching on the
power distribution grid.
40 Hz … 60 Hz
47.5 Hz
HzCtlOpMax
Maximum power frequency for switching on the
power distribution grid.
50 Hz … 70 Hz 50.05 Hz