9 Parameters

Operating Manual

SC4-63HE-BE-BEN103280

97

9.5 Grid Decoupling / Power Frequency

9.6 Grid Connection

Name

Description

Value / range Default

value

HzRtg

Nominal frequency of the power distribution grid 40 Hz … 62 Hz

50 Hz

HzCtlhhLim

Threshold value for overfrequency in level 2

50 Hz … 70 Hz

55 Hz

HzCtlhhLimTm

Tripping time for overfrequency in level 2

0 s … 5 s

0.1 s

HzCtlhLim

Threshold value for overfrequency in level 1

50 Hz … 70 Hz

51.5 Hz

HzCtlhLimTm

Tripping time for overfrequency in level 1

0 s … 5 s

0.1s

HzCtllLim

Threshold value for underfrequency level 1

40 Hz … 60 Hz

47.5 Hz

HzCtllLimTm

Tripping time for underfrequency in level 1

0 s … 600 s

0.1 s

HzCtlllLim

Threshold value for underfrequency in level 2

40 Hz … 60 Hz

46 Hz

HzCtlllLimTm

Tripping time for underfrequency level 2

0 s … 600 s

0.1 s

HzCtlMin

Threshold value for underfrequency level 3

40 Hz … 60 Hz

44 Hz

HzCtlMinTm

Tripping time for underfrequency level 3

0 s … 600 s

0.1 s

Name

Description

Value / range Default

value

GriGrdMonTm Time span in which the activation conditions must

be satisfied so that the power distribution grid can
be switched.

0 ms … 600 ms

5 s

VCtlOpMinNom Minimum grid voltage for switching on the power

distribution grid. The parameter is based on the
nominal voltage "VRtg".

0% … 100%

95%

VCtlOpMaxNom Maximum grid voltage for switching on the power

distribution grid. The parameter is based on the
nominal voltage "VRtg".

100% … 200%

115%

HzCtlOpMin

Minimum power frequency for switching on the
power distribution grid.

40 Hz … 60 Hz

47.5 Hz

HzCtlOpMax

Maximum power frequency for switching on the
power distribution grid.

50 Hz … 70 Hz 50.05 Hz