4.8.11 "VArCtlVol" Procedure

Reactive power is set depending on the grid voltage. The reactive power target value is adjusted in
stages.

Figure 17: Curve for reducing reactive power depending on grid voltage

If the grid voltage and the parameterizable voltage difference "Q-VDif" change for the configurable
duration of "Q-VDifTm", the reactive power target value is adapted to the "Q-VArGra" value.
The parameterization of this function depends on the medium voltage.

Parameter protection

Contact the SMA Serviceline before selecting or parameterizing this procedure.

Used parameters

Q-VDif
Q-VArGra
Q-VDifTm
Q-VRtgOfsNom