7 Troubleshooting

SMA Solar Technology AG

82

SC4-63HE-BE-BEN103280

Operating Manual

201

Error text:
Ground fault or Overtemperature

Error type 2

Failure cause:

• The overtemperature failure chain is interrupted (refer to the circuit diagram).
• Switch cabinet overtemperature
• Transformer overtemperature
• Diode overtemperature
• The insulation resistance of the PV plant is lower than the set limiting value.
• GFDI tripped

Corrective measures:

• Check the cooling fans for proper function.
• Clean or replace dirty air filters.
• Ambient or cooling air temperature too high.
• Check the insulation resistance of the PV array.
• In the event of an insulation fault, separate and connect individual strings to detect the

faulty one.

• Check the function of the ground fault monitoring system.
• Check GFDI (see section 7 "Troubleshooting", page 75 and additional

documentation in the download area of SMA Solar Technology AG at
www.SMA.de/en).

206

Error text:
Emergency shutdown activated

Error type 4

Failure cause:
The device's own emergency shut-off was activated.
Corrective measures:
Unlock emergency and confirm failure (see section 7.6 "Confirming Errors", page 88).

209

Error text:
DC Short circuit

Error type 4

Failure cause:
An internal short circuit was detected on the DC side within the inverter. The DC main switch
was switched off.
Corrective measures:

• Check the Sunny Central from the outside.
• If possible, the Sunny Central should be externally disconnected.
• Contact the SMA Serviceline.