4 grid connection after correction of error, Grid connection after correction of error – SMA SC 400HE User Manual

Page 57

background image

SMA Solar Technology AG

4 Sunny Central Control

Operating Manual

SC4-63HE-BE-BEN103280

57

Figure 19: Tripping characteristics and time-dependant performance illustrated based on the frequency

monitoring

1. Enter password (see section 4.2.2 "Entering the Password", page 32).
2. Select Device Set-up > Parameters > Grid decoupling > Grid frequency.
3. Using the [ ↓ ] button, select the parameter to be changed.
4. Enter the parameter and confirm with [ENTER] until the line stops flashing.
5. Enter the calculated value for offset and confirm with [ENTER] until the line stops flashing.
6. After exiting the menu, confirm the security prompt twice with [ENTER].

☑ Grid monitoring is configured.

4.9.4 Grid Connection after Correction of Error

If a grid fault in the inverter has been corrected, the inverter will only switch on when the grid voltage
meets a set of conditions.
For example, the grid voltage must stay within the set limiting values for grid connection
(e.g., parameter "VCtlOpMinNom") for the duration of the grid monitoring time "GriGrdMonTm".