7 Troubleshooting

Operating Manual

SC4-63HE-BE-BEN103280

85

402

Error text:
Ser. com. with inverter bridge disturbed

Error type 2

Failure cause:

• The RS485 communication between the inverter bridge and the Sunny Central Control

is interrupted.

• The inverter bridge or the Sunny Central Control may be faulty.

Corrective measures:

• Check the RS485 wiring.
• Contact the SMA Serviceline if the error persists.

408

Error text:
PV Overvoltage

Error type 3

Failure cause:
DC voltage is too high on the generator side.
Corrective measures:

• Immediately disconnect the PV array from the Sunny Central! Danger of damage to

the Sunny Central!

• Check the DC voltage.
• Check module wiring and plant design.

Information:

• If the failure poses a danger to the PV plant or the Sunny Central, the Sunny Central

switches into the "Waiting" operating state for 30 minutes.

409

Error text:
IGBT Stack Temperature

Error type 3

Failure cause:
Heat sink temperature is too high (software).
Corrective measures:

• Check the function of the inverter bridge cooling fans.
• Clean soiled air inlet or heat sink.
• Ambient or cooling air temperature too high.
• Contact the SMA Serviceline if the error occurs frequently.