beautypg.com

SMA SC 400HE User Manual

Page 78

background image

7 Troubleshooting

SMA Solar Technology AG

78

SC4-63HE-BE-BEN103280

Operating Manual

284

Error text:
Temperature sensor

Error type 1

Failure cause:
External or internal or temperature sensor is defective.
Corrective measure:

• Check sensors.

380

Error text:
SMU

Error type 1

Failure cause:
The string monitoring system has detected one or more faulty strings or surge arresters.
Corrective measures:

• In the menu "Device Set-up > SMUs > Devices > Measured Values", the individual

string currents can be read out to detect the faulty string.

• More detailed information can be found in the Sunny String-Monitor manual.

381

Error text:
Ser. com. with SMU disturbed

Error type 1

Failure cause:
Communication disturbed between Sunny Central and the Sunny String-Monitors.
Corrective measures:

• Check communication lines and terminals.
• More detailed information can be found in the Sunny String-Monitor manual.

382

Error text:
Thievery solar panel

Error type 1

Failure cause:
Signal loop for theft detection at the Sunny String-Monitor has been interrupted.
Corrective measures:

• Check string currents.
• Check signal loop.
• For further details, refer to the installation guide and user manual of the

Sunny String-Monitor or Sunny String-Monitor Cabinet.

No.

Description

This manual is related to the following products: