3 outp.react.pow, Outp.react.pow – SMA SC 400HE User Manual

Page 93

background image

SMA Solar Technology AG

9 Parameters

Operating Manual

SC4-63HE-BE-BEN103280

93

9.3 Outp.react.pow.

Pmax

*

Limits the active power
This is necessary, for
example, if the feed-in
power has to be limited at
the grid node.

1 kW …

1 000 kW

SC 400HE-11

440 kW

1 kW …

1 000 kW

SC 500HE-11

550 kW

1 kW …

1 000 kW

SC 630HE-11

700 kW

P-HzStop

Frequency for
discontinuing active
power limitation in case of
overfrequency

40 Hz … 70 Hz

50.05 Hz

P-HzStr

Start frequency for limiting
active power in case of
overfrequency

40 Hz … 70 Hz

50.2 Hz

P-WGra

Accepts the active power
as of "P-HzStr"

1%/Hz …

100%/Hz

40 %/Hz

Name

Description

Value / range Explanation

Default
value

Q-VArMod

*

Procedure for the reactive
power setpoint

Off

Sets reactive power
Q = 0 kVAr and
power factor
cos φ = 1

Off

VArCtlCom

Sets reactive power
via Power Reducer
Box

PFCtlCom

Power Reducer Box
transmits power
factor and excitation
of the Sunny Central

VArCnst

Sets "Q-VAr" via
Sunny WebBox or
Sunny Data

VArCnstNom

Sets "Q-VAr-Nom" as
a percentage, with
respect to the nominal
active power, via the
Sunny WebBox or
Sunny Data Control

Name

Description

Value / range Explanation

Default
value