4.8.12 Displaying Error Messages and Warnings for the Reactive

Power Setpoint

The "Q-VArModFailStt" channel shows the error messages or warnings associated with the reactive
power setpoint

Displaying the "Q-VArModFailStt" channel

• Select Spot Values > Outp.react.pow. > Q-VArModFailStt.

Display

Description

Measure

Off

No procedure for specifying the reactive
power setpoint has been chosen.

None

OK

A procedure for specifying the reactive
power setpoint has been chosen and
there are no errors.

None

ComFail

The "VArCtlCom" or "PFCtlCom"
procedure has been chosen and the
expected signal with a valid reactive
power setpoint has been absent for at
least 5 minutes.

• Check whether

Sunny Central Control is working.

• Check whether the

Sunny Central Control can be
accessed from outside and is
displaying the data of the inverter.

• Check whether the cables

between the
Sunny Central Control and the
inverters are OK.

• Check whether the cables inside

the Sunny Central Control are OK.

AnInFail

The "VArCnstNomAnIn" or
"PFCnstNomAnIn" procedure has been
chosen and the value measured at the
analog input is less than 2 mA.

• Check the analog input.