9 Parameters
SMA Solar Technology AG
96
SC4-63HE-BE-BEN103280
Operating Manual
9.4 Grid Decoupling / Voltage
Name
Description
Value / range
Explanation
Default
value
VRtg
Nominal voltage of the
power distribution grid
100 V … 40 000 V
20 000 V
VCtlhLim
Threshold value for
overvoltage in level 1
100% … 150%
115%
VCtlhLimTm
Tripping time for threshold
value during overvoltage in
level 1
0 s … 5 s
0.1 s
VCtlhhLim
Threshold value for
overvoltage in level 2
100% … 150%
130%
VCtlhhLimTm
Tripping time for threshold
value during overvoltage in
level 2
0 s … 5 s
0.1 s
VCtllLim
Threshold value for
undervoltage in level 1
0% … 100%
80%
VCtllLimTm
Tripping time for threshold
value during undervoltage
in level 1
0 s … 5 s
0.1 s
VCtlllLim
Threshold value for
undervoltage in level 2
0% … 100%
45%
VCtlllLimTm
Tripping time for threshold
value during undervoltage
in level 2
0 s … 5 s
0.1 s
TrfVolExlHi
Line-to-line voltage on the
overvoltage side of the
external transformer
0 V … 65 535 V
20 000 V
TrfVolExlLo
Line-to-line voltage on the
undervoltage side of the
external transformer
SC 400HE-11
270 V
SC 500HE-11
270 V
SC 630HE-11
315 V