background image

9 Parameters

SMA Solar Technology AG

96

SC4-63HE-BE-BEN103280

Operating Manual

9.4 Grid Decoupling / Voltage

Name

Description

Value / range

Explanation

Default
value

VRtg

Nominal voltage of the
power distribution grid

100 V … 40 000 V

20 000 V

VCtlhLim

Threshold value for
overvoltage in level 1

100% … 150%

115%

VCtlhLimTm

Tripping time for threshold
value during overvoltage in
level 1

0 s … 5 s

0.1 s

VCtlhhLim

Threshold value for
overvoltage in level 2

100% … 150%

130%

VCtlhhLimTm

Tripping time for threshold
value during overvoltage in
level 2

0 s … 5 s

0.1 s

VCtllLim

Threshold value for
undervoltage in level 1

0% … 100%

80%

VCtllLimTm

Tripping time for threshold
value during undervoltage
in level 1

0 s … 5 s

0.1 s

VCtlllLim

Threshold value for
undervoltage in level 2

0% … 100%

45%

VCtlllLimTm

Tripping time for threshold
value during undervoltage
in level 2

0 s … 5 s

0.1 s

TrfVolExlHi

Line-to-line voltage on the
overvoltage side of the
external transformer

0 V … 65 535 V

20 000 V

TrfVolExlLo

Line-to-line voltage on the
undervoltage side of the
external transformer

SC 400HE-11

270 V

SC 500HE-11

270 V

SC 630HE-11

315 V