SMA Solar Technology AG

7 Troubleshooting

Operating Manual

SC4-63HE-BE-BEN103280

79

601

Error text:
Defective default Effective power

Error type 1

Failure cause:
The current value present at the analog input is not within the permitted range.
Corrective measures:

• Check the analog input.

602

Error text:
Defective default Reactive power.

Error type 1

Failure cause:
The current value present at the analog input is not within the permitted range.
Corrective measures:

• Check the analog input.

603

Error text:
Disturbed communication Effective power

Error type 1

Failure cause:
Preset signal at the communication level is faulty.
Corrective measures:

• Check the communication route.

604

Error text:
Disturbed communication Reactive power.

Error type 1

Failure cause:
Preset signal at the communication level is faulty.
Corrective measures:

• Check the communication route.

680

Error text:
External Alarm was initiated

Error type 1

Failure cause:
Depending on the unit being monitored.
Corrective measures:
Check the unit connected on at external alarm input.