7 Troubleshooting
Operating Manual
SC4-63HE-BE-BEN103280
79
601
Error text:
Defective default Effective power
Error type 1
Failure cause:
The current value present at the analog input is not within the permitted range.
Corrective measures:
• Check the analog input.
602
Error text:
Defective default Reactive power.
Error type 1
Failure cause:
The current value present at the analog input is not within the permitted range.
Corrective measures:
• Check the analog input.
603
Error text:
Disturbed communication Effective power
Error type 1
Failure cause:
Preset signal at the communication level is faulty.
Corrective measures:
• Check the communication route.
604
Error text:
Disturbed communication Reactive power.
Error type 1
Failure cause:
Preset signal at the communication level is faulty.
Corrective measures:
• Check the communication route.
680
Error text:
External Alarm was initiated
Error type 1
Failure cause:
Depending on the unit being monitored.
Corrective measures:
Check the unit connected on at external alarm input.