Procedure for Regulating Reactive Power and Setting Associated Parameters

1. Enter password (see section 4.2.2 "Entering the Password", page 32).
2. Device Set-up > Parameters > Red.effect.pow. Select > P-WMod.

☑ Line below "P-WMod" flashes.

3. Select the required procedure for limiting the active power.
4. Press [ENTER] twice.

☑ The required procedure for limiting the active power is set.

5. If necessary, select the parameter pertaining to the procedure with the [ ↓ ] key and press

[ENTER].

6. Set the parameter.
7. Press [ENTER] twice.

4.8.2 "Off" Procedure

The reactive power target value is limited to 0 kVAr. This target value cannot be influenced.

4.8.3 "VArCtlCom" Procedure

The reactive power target value is received by the Sunny Central Control through the Power Reducer
Box and forwarded to the Sunny Central. The target value is detected as a percentage and converted
to kVAr inside the device.
If the Sunny Central has received no signal for 5 minutes, the "P-ModFailStt" error message will be
displayed.

4.8.4 "PFCtlCom" Procedure

The reactive power target value is received by the Sunny Central Control through the Power Reducer Box
and forwarded to the Sunny Central. A power factor is transmitted as a predefined target value.
If the Sunny Central has received no signal for 5 minutes, the "P-ModFailStt" error message will be
displayed.

Used parameters

none

Used parameters

none

Used parameters

none