7 Troubleshooting

Operating Manual

SC4-63HE-BE-BEN103280

81

110

Error text:
UVW-Range

Error type 2

Failure cause:
Voltage on phase L1, L2, or L3 outside the permitted range.
Corrective measures:

• Check grid connections.
• Check grid stability.

111

Error text:
Grid frequency too high or too low

Error type 2

Failure cause:
Grid limits were breached.
Corrective measures:

• Check the display of the grid monitoring relay.
• Check the fuses in the load circuit.

112

Error text:
External Grid Monitoring tripped

Error type 2

Failure cause:
Voltage or frequency on the AC side is outside the permitted range.
Corrective measures:

• Check the grid connections.
• Check grid stability.
• Check right-hand rotary field.