7 Troubleshooting
Operating Manual
SC4-63HE-BE-BEN103280
81
110
Error text:
UVW-Range
Error type 2
Failure cause:
Voltage on phase L1, L2, or L3 outside the permitted range.
Corrective measures:
• Check grid connections.
• Check grid stability.
111
Error text:
Grid frequency too high or too low
Error type 2
Failure cause:
Grid limits were breached.
Corrective measures:
• Check the display of the grid monitoring relay.
• Check the fuses in the load circuit.
112
Error text:
External Grid Monitoring tripped
Error type 2
Failure cause:
Voltage or frequency on the AC side is outside the permitted range.
Corrective measures:
• Check the grid connections.
• Check grid stability.
• Check right-hand rotary field.