SMA SC 400HE User Manual
Page 95
SMA Solar Technology AG
9 Parameters
Operating Manual
SC4-63HE-BE-BEN103280
95
* Only modify parameters after consultation with SMA Solar Technology AG.
PF-PFStop
*
Power factor cos φ at the
point "PF-WStop"
0.5 … 1
1
PF-PFExtStop
*
Excitation of the power
factor cos φ at the point
"PF-WStop"
Overexcited
Overexcited
Overexcited
Underexcited
Underexcited
PF-WStr
*
Feed-in power in % at the
point "PF-WStr"
0% … 90%
0%
PF-WStop
*
Feed-in power in % at the
point "PF-WStop"
10% … 100%
100%
Q-VDif
*
Reactive power
depending on the nominal
voltage "VRtg"
0.1% … 10%
1%
Q-VArGra
*
Reactive power target
value in % of the nominal
power "Pmax" at a
voltage step "Q-VDif"
0% … 100%
1%
Q-VDifTm
*
Time span of a voltage
step "Q-VDif" in which it
must wait before the
reactive power target
value "Q-VArGra"
changes
0 s … 120 s
1 s
Q-VRtgOfs
Nom
*
Change in the nominal
voltage for testing
purposes in % based on
"VRTg". It is only active
when the "QVArMod"
parameter is at
"VArCtlCol".
‒10% … +10%
0%
Name
Description
Value / range Explanation
Default