2 red.effect.pow, Red.effect.pow – SMA SC 400HE User Manual

Page 92

background image

9 Parameters

SMA Solar Technology AG

92

SC4-63HE-BE-BEN103280

Operating Manual

9.2 Red.effect.pow.

Name

Description

Value / range Explanation

Default
value

P-WMod

Target value for active
power limitation
procedure

Off

Limits active power to
"Pmax"

Off

WCtlCom

Limits active power via
an external control unit,
such as the Power
Reducer Box

WCnst

Manually limits the
active power (P-W) via
the Sunny WebBox or
Sunny Data Control

WCnstNom

Manually limits the
active power P-WNom
via the Sunny WebBox
or Sunny Data Control

WCnstNomAnln Limits active power on

the analog input
"ExtSolP"

P-W

Limits the active power
in kW

0 kW …

1 000 kW

SC 400HE-11

440 kW

0 kW …

1 000 kW

SC 500HE-11

550 kW

0 kW …

1 000 kW

SC 630HE-11

700 kW

P-WNom

Limits the active power
in %

0% … 100%

100%

Pac nominal

Nominal active power of
the Sunny Central

1 kW …

1 000 kW

SC 400HE-11

440 kW

1 kW …

1 000 kW

SC 500HE-11

550 kW

1 kW …

1 000 kW

SC 630HE-11

700 kW

Smax

*

Maximum apparent
power that the
Sunny Central feeds into
the grid during nominal
operation

0 kVA …

1 000 kVA

SC 400HE-11

440 kVA

0 kVA …

1 000 kVA

SC 500HE-11

550 kVA

0 kVA …

1 000 kVA

SC 630HE-11

700 kVA