5 Insulation Monitoring
SMA Solar Technology AG
60
SC4-63HE-BE-BEN103280
Operating Manual
5.2.2 Switching between the Main Menu and Standard Operation
• Press the [MENU] button to switch to the main menu from standard operation. You can enter
various submenus from the main menu.
• To return to standard operation, press [RESET].
5.2.3 Selecting used PV Modules
There are various measurement profiles available for the insulation monitoring. Select the
measurement profile that is suitable for your PV modules.
1. Access main menu.
2. Select the ISO ADVANCED menu and then select the Measure menu.
3. Select the measurement profile that matches the PV modules and confirm by pressing [ENTER].
C
[RESET] button
Deletes saved insulation error alarms
Down button
Changes parameter, moves down in the
menu
Lowers a parameter
D
[MENU] button
Call up menu system
[ENTER] button
Confirms parameter change
E
Alarm LED 1 turns on
Insulation error, first warning threshold is
reached
F
Alarm LED 2 turns on
Insulation error, second warning
threshold is reached
G
Device fault LED turns on
iso-PV is faulty
H
2-line display for standard and menu
operation
Module types
Measurement profile
PV modules with crystalline cells
AMP3
PV modules with thin-film cells
AMP4
Other PV modules
AMP
Position
Description
Function